作者: Li Yang , Wen Wang
DOI: 10.1016/J.IJREFRIG.2010.07.011
关键词: Refrigerant 、 Thermodynamics 、 Refrigeration 、 Tube (fluid conveyance) 、 Distributor 、 Heat transfer 、 Heat exchanger 、 Evaporator 、 Materials science 、 Mechanics 、 Volumetric flow rate
摘要: The performance of the horizontal heat transfer tube bundles in falling film evaporators large compression refrigeration systems was investigated with numerical simulation this paper. Four types tubes, including plain and enhanced surface tubes Turbo-B, Turbo-BII Turbo-EHP, were employed simulation. Some factors, such as kind, pass arrangement, dry patch area on surface, liquid refrigerant flow rate, number flooded analyzed based simulated results. In study, maldistribution caused by distributor apparatus discussed, which severely affects according to calculated results verified experiment. These discussions can be used guide design under realistic conditions.