Efficient voltage regulation scheme for three-phase self-excited induction generator feeding single-phase load in remote locations

作者: Sarsing Gao , Gurumoorthy Bhuvaneswari , Shikaripur S Murthy , Ujjwal Kalla , None

DOI: 10.1049/IET-RPG.2012.0204

关键词: EngineeringThree-phaseElectronic engineeringVoltage regulationDuty cycleInduction generatorRectifierControl theoryInsulated-gate bipolar transistorControl theoryPulse-width modulation

摘要: This study presents analysis, design and implementation of a microcontroller based electronic load controller (ELC) for efficient voltage regulation three-phase self-excited induction generator (SEIG) feeding single-phase loads in remote locations. The proposed ELC has an uncontrolled rectifier, filtering capacitor, insulated gate bipolar transistor switch series dump load. pulse-width modulation (PWM) pulses with appropriate duty cycle are generated using the dsPIC30F6010 microcontroller. ratio is determined on closed-loop control scheme which decides amount power diverted to SEIG–ELC system demonstrates effective switching between main thereby providing at machine terminals. modelled Matlab/Simulink simulated results validated by experimental results.

参考文章(13)
D. K. Palwalia, S. P. Singh, Digital Signal Processor-based Controller Design and Implementation for Self-excited Induction Generator Electric Power Components and Systems. ,vol. 36, pp. 1130- 1140 ,(2008) , 10.1080/15325000802046959
J.L. Bhattacharya, J.L. Woodward, Excitation balancing of a self-excited induction generator for maximum power output IEE Proceedings C Generation, Transmission and Distribution. ,vol. 135, pp. 88- 97 ,(1988) , 10.1049/IP-C.1988.0011
Sarsing Gao, Abhishek Kumar, Mitigation of unbalanced currents in three-phase asynchronous generator supplying single-phase nonlinear load ieee international conference on sustainable energy technologies. pp. 246- 251 ,(2012) , 10.1109/ICSET.2012.6357406
A.K. Tandon, S.S. Murthy, G. Berg, Steady State Analysis of Capacitor Self-Excited Induction Generators IEEE Power & Energy Magazine. ,vol. 103, pp. 612- 618 ,(1984) , 10.1109/TPAS.1984.318748
Azzeddine Benlamoudi, Rachid Abdessemed, STATCOM based voltage-frequency regulation for SEIG driven by an uncontrolled speed turbine International Journal of Power and Energy Conversion. ,vol. 1, pp. 399- ,(2009) , 10.1504/IJPEC.2009.029057
S.S. Murthy, A novel self-induced self-regulated single phase induction generator. I. Basic system and theory IEEE Transactions on Energy Conversion. ,vol. 8, pp. 377- 382 ,(1993) , 10.1109/60.257048
Vishal Verma, Peeyush Pant, Bhim Singh, VSC supported active load control for SEIG under load perturbations India International Conference on Power Electronics 2010 (IICPE2010). pp. 1- 6 ,(2011) , 10.1109/IICPE.2011.5728150
JA Barrado, R Grino, H Valderrama-Blavi, None, Power-Quality Improvement of a Stand-Alone Induction Generator Using a STATCOM With Battery Energy Storage System IEEE Transactions on Power Delivery. ,vol. 25, pp. 2734- 2741 ,(2010) , 10.1109/TPWRD.2010.2051565
S.S. Murthy, B. Singh, S. Gupta, B.M. Gulati, General steady-state analysis of three-phase self-excited induction generator feeding three-phase unbalanced load/single-phase load for stand-alone applications IEE Proceedings - Generation, Transmission and Distribution. ,vol. 150, pp. 49- 55 ,(2003) , 10.1049/IP-GTD:20030072
D. Henderson, An advanced electronic load governor for control of micro hydroelectric generation IEEE Transactions on Energy Conversion. ,vol. 13, pp. 300- 304 ,(1998) , 10.1109/60.707611