DETERMINATION OF ACTUAL REDUCTION FACTOR OF HV AND MV CABLE LINES PASSING THROUGH URBAN AND SUBURBAN AREAS

作者: Ljubivoje Popovic

DOI: 10.2298/FUEE1401025P

关键词: Compensation (engineering)Power (physics)Reduction factorMarine engineeringFault (power engineering)Line (geometry)Current distributionEngineeringElectrical engineeringMagnet

摘要: The paper presents the method for determination of ground fault current distribution in cases when feeding cable lines are passing through urban and/or suburban areas, or many relevant data uncertain, completely unknown. problem appears as a consequence fact that surrounding installations situated under surface and cannot be visually determined verified. On basis on site measurements, developed enables compensation all deficiencies about metal involved with fluctuating magnet field appearing along around power line during an unbalanced fault. presented analytical procedure is based certain  measurable quantities cumulatively involve inductive effects all, known unknown installations. performed quantitative analysis points at significance taking into account existence

参考文章(10)
Lj.M. Popović, Testing and evaluating grounding systems for substations located in urban areas Iet Generation Transmission & Distribution. ,vol. 5, pp. 231- 238 ,(2011) , 10.1049/IET-GTD.2009.0665
L.M. Popovic, Practical method for evaluating ground fault current distribution in station, towers and ground wire IEEE Transactions on Power Delivery. ,vol. 13, pp. 123- 128 ,(1998) , 10.1109/61.660868
F. Dawalibi, George Niles, Measurements and Computations of Fault Current Distribution on Overhead Transmission Lines IEEE Power & Energy Magazine. ,vol. 3, pp. 553- 560 ,(1984) , 10.1109/TPAS.1984.318744
S.T. Sobral, J.A. Barbosa, J.V.C. Nunes, E. Chinelli, A. Ferreira Netto, V.S. Costa, J. Hisbello Campos, Ground potential rise characteristics of urban step-down substations fed by power cables-a practical example IEEE Transactions on Power Delivery. ,vol. 3, pp. 1564- 1572 ,(1988) , 10.1109/61.193956
Janos Endrenyi, Analysis of Transmission Tower Potentials During Ground Faults IEEE Transactions on Power Apparatus and Systems. ,vol. 10, pp. 1274- 1283 ,(1967) , 10.1109/TPAS.1967.291904
Ljubivoje M. Popović, Transfer characteristics of electric-power lines passing through urban and suburban areas International Journal of Electrical Power & Energy Systems. ,vol. 56, pp. 151- 158 ,(2014) , 10.1016/J.IJEPES.2013.11.011
L.M. Popovic, Determination of the reduction factor for feeding cable lines consisting of three single-core cables IEEE Transactions on Power Delivery. ,vol. 18, pp. 736- 743 ,(2003) , 10.1109/TPWRD.2003.813814
L.M. Popovic, Efficient reduction of fault current through the grounding grid of substation supplied by cable line IEEE Transactions on Power Delivery. ,vol. 15, pp. 556- 561 ,(2000) , 10.1109/61.852984