Fault current distribution in HV cable systems

作者: E. Viel , H. Griffiths

DOI: 10.1049/IP-GTD:20000404

关键词: EngineeringParametric statisticsReturn currentElectronic circuitElectrical impedanceMagnitude (mathematics)Distribution (mathematics)Electrical engineering

摘要: An advanced analytical model is presented for the evaluation of ground return currents at substations fed by both three and single-core cable circuits. The circuit includes accurate treatment an intermediate substation between source faulted substation, unlike Engineering Recommendation EA S.34, which adopts a more simplified approach. Through detailed parametric studies, differences are quantified. effects that variations in key parameters — length type, earth impedances have on magnitude current identified explained.

参考文章(5)
R. Verma, D. Mukhedkar, Ground Fault Current Distribution in Sub-Station, Tower and Ground Wire IEEE Transactions on Power Apparatus and Systems. ,vol. 3, pp. 724- 730 ,(1979) , 10.1109/TPAS.1979.319276
J. Nahman, V. Dordević, Distribution of zero sequence currents for earth faults occurring along a transmission line and proximity effects IEE Proceedings C Generation, Transmission and Distribution. ,vol. 140, pp. 427- 432 ,(1993) , 10.1049/IP-C.1993.0062
A. N. Guven, S. A. Sebo, Analysis of Ground Fault Curreni Distribuiion along Underground Cables IEEE Power & Energy Magazine. ,vol. 1, pp. 22- 23 ,(1986) , 10.1109/TPWRD.1986.4308024