Loss-of-mains detection for small generators

作者: P.D. Hopewell , N. Jenkins , A.D. Cross

DOI: 10.1049/IP-EPA:19960286

关键词: VoltageOutput impedanceInterconnectionSynchronizationTrippingMains electricityGenerating set of a groupEngineeringElectronic engineeringCommutation

摘要: A new loss-of-mains detection method for use with very small generators is proposed. known load repeatedly switched on to the supply, and resulting voltage changes used estimate source impedance, hence detect loss of mains. Correlating switching change prevents false operation arising from random changes. Experiments simulations are discussed which demonstrate principles technique. Test results presented show that technique operates correctly, can reliably a mains without being susceptible tripping.

参考文章(1)
N.W. Lane, D.M. Berchowitz, D. Shade, A. Karandikar, Development of a high frequency Stirling engine-powered 3 kW(e) generator set intersociety energy conversion engineering conference. pp. 2213- 2218 ,(1989) , 10.1109/IECEC.1989.74781