Fast detector of symmetrical fault during power swing for distance relay

作者: B. Su , X.Z. Dong , Z.Q. Bo , Y.Z. Sun , B.R.J. Caunce

DOI: 10.1109/PES.2005.1489209

关键词: VoltageEmtpSwingEngineeringFault indicatorDetectorElectrical engineeringStuck-at faultPower (physics)Electronic engineeringFault (power engineering)

摘要: Distance relay should be blocked during power swing to ensure the reliability, but still trip as soon possible after an internal fault occurs swing. It was very difficult detect symmetrical reliably and fast with complex conditions considered. This paper presents a new detector of Based on sudden reduction absolute value change rate centre voltage (PSCV), presented can sensitively in two cycles. is easy set immune period, arc, location angle. EMTP simulations real-time digital simulator system (RTDS) tests prove fast, sensible reliable.

参考文章(3)
A.T. Johns, Improved techniques for modelling fault arcs an faulted EHV transmission systems IEE Proceedings - Generation, Transmission and Distribution. ,vol. 141, pp. 148- 154 ,(1994) , 10.1049/IP-GTD:19949869
D Hou, G Benmouyal, DA Tziouvaras, Zero-setting power-swing blocking protection 3rd IEE International Conference on Reliability of Transmission and Distribution Networks (RTDN 2005). pp. 249- 254 ,(2005) , 10.1049/CP:20050047
M. Kizilcay, T. Pniok, Digital simulation of fault arcs in power systems European Transactions on Electrical Power. ,vol. 1, pp. 55- 60 ,(2007) , 10.1002/ETEP.4450010111