Operator-Friendly Technique and Quality Control Considerations for Indigo Colorimetric Measurement of Ozone Residual

作者: Kerwin L. Rakness , Eric C. Wert , Michael Elovitz , Suzanne Mahoney

DOI: 10.1080/01919510903467864

关键词: Water treatmentChemistryQuality (business)Process engineeringCalibrationOzoneResidualQuality assuranceSample (material)Measure (data warehouse)Environmental engineering

摘要: Drinking water ozone disinfection systems measure residual concentration, C, for regulatory compliance reporting of concentration-times-time (CT), and the resultant log-inactivation virus, Giardia Cryptosporidium. The indigotrisulfonate (ITS) colorimetric procedure is Standard Method measuring residual. Although currently written relatively easy to implement, its accuracy depends on specific ITS quality control considerations. based upon quantities materials sample volumes, which make it somewhat inflexible. Tests are often performed in plant surroundings by operating staff, as opposed certified laboratories analytical chemists. In this paper, a more flexible, quality-assured “operator-friendly” technique presented method. This manuscript investigates several aspects method (e.g. effects aging, storage temperature, supplier, weight measurement, manganes...

参考文章(7)
Gilbert Gordon, Renee D. Gauw, Yuko Miyahara, Bryan Walters, Bernard Bubnis, Using indigo absorbance to calculate the indigo sensitivity coefficient Journal - American Water Works Association. ,vol. 92, pp. 96- 100 ,(2000) , 10.1002/J.1551-8833.2000.TB09074.X
Andrew Eaton, A.E. Greenberg, Lenore S. Clesceri, Standard methods for the examination of water and wastewater Published in <b>1998</b> in Washington DC) by American public health association. ,(1992)
H. Bader, J. Hoigné, Determination of ozone in water by the indigo method Water Research. ,vol. 15, pp. 449- 456 ,(1981) , 10.1016/0043-1354(81)90054-3
Richard S Yates, Michael K Stenstrom, Gravimetric sampling procedure for aqueous ozone concentrations Water Research. ,vol. 34, pp. 1413- 1416 ,(2000) , 10.1016/S0043-1354(99)00263-8
Gilbert Gordon, Bernard Bubnis, Residual Ozone Measurement: Indigo Sensitivity Coefficient Adjustment Ozone-science & Engineering. ,vol. 24, pp. 17- 28 ,(2002) , 10.1080/01919510208901591
H. Bader, Determination of Ozone In Water By The Indigo Method: A Submitted Standard Method Ozone-science & Engineering. ,vol. 4, pp. 169- 176 ,(1982) , 10.1080/01919518208550955
Jürg Hoigné, Heinz Bader, BESTIMMUNG VON OZON UND CHLORDIOXID IN WASSER MIT DER INDIGO-METHODE Vom Wasser. pp. 261- 280 ,(1980)