作者: M. Jones , A. Moses , J. Thompson
DOI: 10.1109/TMAG.1973.1067577
关键词: Wattmeter 、 Transformer 、 Geometry 、 Flux distribution 、 Flux 、 Physics 、 Nuclear magnetic resonance 、 Energy efficient transformer 、 Power loss
摘要: The design of the joints in a power transformer core has marked influence on efficiency as whole. Two experimental cores have been built such that lengths their 45° mitered overlaps could be varied from 0 to 2.0 cm. larger core, with 1.0 m limbs, was used for investigating flux and loss variations second, smaller study how results might affected by changes dimensions. For measured two ways range overlaps: first, using localized technique, then measuring total precision wattmeter. In both cases, minimum found when an overlap 0.5 length again found, but cm overlap. A change over 20% used, optimum independent density T 1.8 T. special distribution determined array search coils. enables qualitative explanation occurrence loss.