A Novel, Low-Cost, Reduced-Sensor Approach for Providing Smart Renote Monitoring and Diagnostics for Packaged Air Conditioners and Heat Pumps

作者: Michael R. Brambley

DOI: 10.2172/967227

关键词: Efficient energy useElectrical loadFault detection and isolationCapital costAutomotive engineeringControl engineeringHeat pumpGas compressorEngineeringAir conditioningPower (physics)

摘要: This report describes conceptually an approach to providing automated remote performance and conditioning monitoring fault detection for air conditioners heat pumps that shows great promise reduce the capital installation costs of such systems from over $1000 per unit $200 $400 unit. The relies on non-intrusive electric load (NIELM) enable separation power use signals compressors fans in conditioner or pump. Then combining information uses one two temperature measurements, changes energy efficiency occurrence major faults would be detected. By decreasing number sensors used between ten twenty current diagnostic three envisaged system, cost system hardware labor decreased significantly. After describing problem being addressed concept more detail, identifies specific conditions proposed method detect, discusses needs successful NIELM approach, elements path a commercialized system.

参考文章(8)
S. R. Shaw, C. B. Abler, R. F. Lepard, D. Luo, S. B. Leeb, L. K. Norford, Instrumentation for High Performance Nonintrusive Electrical Load Monitoring Journal of Solar Energy Engineering. ,vol. 120, pp. 224- 229 ,(1998) , 10.1115/1.2888073
Peter Armstrong, Christopher Laughman, Steven Leeb, Leslie Norford, Detection of Rooftop Cooling Unit Faults Based on Electrical Measurements Hvac&r Research. ,vol. 12, pp. 151- 175 ,(2006) , 10.1080/10789669.2006.10391172
Christopher Laughman, Kwangduk Lee, Robert Cox, Steven Shaw, Steven Leeb, Les Norford, Peter Armstrong, None, Power signature analysis IEEE Power & Energy Magazine. ,vol. 1, pp. 56- 63 ,(2003) , 10.1109/MPAE.2003.1192027
G.W. Hart, Residential energy monitoring and computerized surveillance via utility power flows IEEE Technology and Society Magazine. ,vol. 8, pp. 12- 16 ,(1989) , 10.1109/44.31557
Leslie K. Norford, Chris R. Laughman, Peter R. Armstrong, Steven B. Leeb, FAULT DETECTION BASED ON MOTOR START TRANSIENTS AND SHAFT HARMONICS MEASURED AT THE RTU ELECTRICAL SERVICE ,(2004)
G.W. Hart, Nonintrusive appliance load monitoring Proceedings of the IEEE. ,vol. 80, pp. 1870- 1891 ,(1992) , 10.1109/5.192069
S. Drenker, A. Kader, Nonintrusive monitoring of electric loads IEEE Computer Applications in Power. ,vol. 12, pp. 47- 51 ,(1999) , 10.1109/67.795138
Srinivas Katipamula, R. Brambley, Diagnostics for Monitoring-Based Commissioning ,(2009)