Using virtual impedance network to improve the control performances of LCL-type grid-connected inverter under the weak grid condition

作者: Dongsheng Yang , Xinbo Ruan , Heng Wu

DOI: 10.1109/APEC.2014.6803739

关键词:

摘要: Under the high penetration of renewable energy, power grid may features as weak grid, which contains a large set impedance values and varies harmonics. The grid-connected inverter can be greatly challenged by this condition when it is operated interface to inject generated into grid. Particularly, stability problem aroused injected current distorted voltage Luckily, output give an insight stable robustness harmonic rejection ability control system, so relationships between them are investigated in paper. Based on which, virtual network proposed provide additional degrees freedom for optimization. With method, exhibits against grid-impedance variation also performs strong background harmonics at same time. Experimental results from LCL-type single-phase confirm theoretical expectations effectiveness solutions.

参考文章(13)
J.H.R. Enslin, P.J.M. Heskes, Harmonic interaction between a large number of distributed power inverters and the distribution network IEEE Transactions on Power Electronics. ,vol. 19, pp. 1586- 1593 ,(2004) , 10.1109/TPEL.2004.836615
Chenlei Bao, Xinbo Ruan, Xuehua Wang, Weiwei Li, Donghua Pan, Kailei Weng, Design of injected grid current regulator and capacitor-current-feedback active-damping for LCL-type grid-connected inverter european conference on cognitive ergonomics. pp. 579- 586 ,(2012) , 10.1109/ECCE.2012.6342769
Juan Luis Agorreta, Mikel Borrega, Jesús López, Luis Marroyo, Modeling and Control of $N$ -Paralleled Grid-Connected Inverters With LCL Filter Coupled Due to Grid Impedance in PV Plants IEEE Transactions on Power Electronics. ,vol. 26, pp. 770- 785 ,(2011) , 10.1109/TPEL.2010.2095429
M. Liserre, R. Teodorescu, F. Blaabjerg, Stability of photovoltaic and wind turbine grid-connected inverters for a large set of grid impedance values IEEE Transactions on Power Electronics. ,vol. 21, pp. 263- 272 ,(2006) , 10.1109/TPEL.2005.861185
H. Deng, R. Oruganti, D. Srinivasan, PWM methods to handle time delay in digital control of a UPS inverter IEEE Power Electronics Letters. ,vol. 3, pp. 1- 6 ,(2005) , 10.1109/LPEL.2004.842402
Sung Yeul Park, Chien Liang Chen, Jih Sheng Lai, Seung Ryul Moon, Admittance Compensation in Current Loop Control for a Grid-Tie LCL Fuel Cell Inverter IEEE Transactions on Power Electronics. ,vol. 23, pp. 1716- 1723 ,(2008) , 10.1109/TPEL.2008.924828
F. Blaabjerg, R. Teodorescu, M. Liserre, A.V. Timbus, Overview of Control and Grid Synchronization for Distributed Power Generation Systems IEEE Transactions on Industrial Electronics. ,vol. 53, pp. 1398- 1409 ,(2006) , 10.1109/TIE.2006.881997
Xuehua Wang, Xinbo Ruan, Shangwei Liu, K Tse Chi, None, Full Feedforward of Grid Voltage for Grid-Connected Inverter With LCL Filter to Suppress Current Distortion Due to Grid Voltage Harmonics IEEE Transactions on Power Electronics. ,vol. 25, pp. 3119- 3127 ,(2010) , 10.1109/TPEL.2010.2077312
Jian Sun, Impedance-Based Stability Criterion for Grid-Connected Inverters IEEE Transactions on Power Electronics. ,vol. 26, pp. 3075- 3078 ,(2011) , 10.1109/TPEL.2011.2136439
Mauricio Cespedes, Jian Sun, Impedance shaping of three-phase grid-parallel voltage-source converters applied power electronics conference. pp. 754- 760 ,(2012) , 10.1109/APEC.2012.6165904