Safety assessment of AC earthing systems in a DC traction-supply substation

作者: C.-H. Lee , S.-D. Lin

DOI: 10.1049/IP-EPA:20045191

关键词:

摘要: The paper assesses safety of AC earthing systems in a DC traction-supply substation (TSS) by comparing the designed mesh and step voltages to maximum tolerable voltages. Generally, IEEE 80 criteria are based on body current prevent fibrillation human heart, this is then translated into touch As result, assessment TSS referred procedure which computed compared with Computation results for orange line at O19 Taipei rapid-transit presented as an example.

参考文章(6)