作者: Wang Jiang-Jiang , Zhang Chun-Fa , Jing You-Yin
DOI: 10.1016/J.APENERGY.2009.06.027
关键词:
摘要: Abstract The design and operation of combined cooling, heating power (CCHP) systems are greatly dependent upon the seasonal atmospheric conditions, which determine thermal demands buildings. This paper presents a mathematical analysis CCHP system in comparison to separate system. corresponding primary energy consumption demand management (TDM) electrical (EDM) modes deduced. Three relative criteria, saving (PES), CO2 emission reduction (CO2ER), annual total cost (ATCS) employed evaluate respective performances for hypothetical building five different climate zones from technical, environmental economic aspects. results indicate that TDM mode cold area, where requires more during year, achieves benefit over while EDM suits having stable mild zone.