Influence of the variable-speed wind generators in transient stability margin of the conventional generators integrated in electrical grids

作者: M.V.A. Nunes , J.A. PecasLopes , H.H. Zurn , U.H. Bezerra , R.G. Almeida

DOI: 10.1109/TEC.2004.832078

关键词:

摘要: This work demonstrates that the integration of variable-speed wind systems with doubly fed induction generators (DFIG) and a four-quadrant AC-to-AC converter connected to rotor windings increases transient stability margin electrical grids, when compared case where fixed speed cage are used. It is due influence two dedicated current regulators DFIG on dynamic behavior other in system. Besides, adequate models represent studies presented. From simulation results, some important conclusions can be extracted guide farms weak or strong grids.

参考文章(14)
Peter Crossley, Nick Jenkins, Goran Strbac, David Kirschen, Ron Allan, Embedded Generation (Power & Energy Ser. 31) ,(2000)
Paul C. Krause, Analysis of Electric Machinery ,(1986)
Paul M. Anderson, Analysis of faulted power systems ,(1973)
Prabha Kundur, Power system stability and control McGraw-Hill. ,(1994)
V Akhmatov, H Knudsen, A.H Nielsen, Advanced simulation of windmills in the electric power supply International Journal of Electrical Power & Energy Systems. ,vol. 22, pp. 421- 434 ,(2000) , 10.1016/S0142-0615(00)00007-7
S. Muller, M. Deicke, R.W. De Doncker, Doubly fed induction generator systems for wind turbines IEEE Industry Applications Magazine. ,vol. 8, pp. 26- 33 ,(2002) , 10.1109/2943.999610
Andrés Feijóo, José Cidrás, Camilo Carrillo, A third order model for the doubly-fed induction machine Electric Power Systems Research. ,vol. 56, pp. 121- ,(2000) , 10.1016/S0378-7796(00)00103-6