Parallel processing inverter system

作者: T. Kawabata , N. Sashida , Y. Yamamoto , K. Ogasawara , Y. Yamasaki

DOI: 10.1109/63.85912

关键词:

摘要: A novel method of instantaneous voltage and power balance control a parallel processing inverter system is proposed. It consists high-speed switching PWM (pulsewidth modulated) with an current minor loop controller, major controller. This realizes the following functions only one inverter: constant AC output reactive control, active filtering to absorb load harmonics, DC as AC-to-DC converter, uninterruptible supply (UPS) for stand-alone operation. covers wide application range, including UPS systems, new energy filters functions. >

参考文章(5)
Phoivos D. Ziogas, Stefanos Manias, Eduardo P. Wiechmann, Application of Current Source Inverters in UPS Systems IEEE Transactions on Industry Applications. ,vol. 20, pp. 742- 752 ,(1984) , 10.1109/TIA.1984.4504483
T. Kawabata, N. Sashida, T. Miyashita, Y. Yamamoto, UPS Systems using Multi-functional Inverters international telecommunications energy conference. pp. 525- 530 ,(1987) , 10.1109/INTLEC.1987.4794609
T. Kawabata, T. Miyashita, Y. Yamamoto, Dead beat control of three phase PWM inverter IEEE Transactions on Power Electronics. ,vol. 5, pp. 21- 28 ,(1990) , 10.1109/63.45996
F.Z. Peng, H. Akagi, A. Nabae, A new approach to harmonic compensation in power systems ieee industry applications society annual meeting. pp. 874- 880 ,(1988) , 10.1109/IAS.1988.25163
Gyugyi Laszlo, Active ac power filters Proc. of the IEEE IAS'76 Annual meeting. pp. 529- 535 ,(1976)