作者: Leonardy Setyawan , Xiao Jianfang , Wang Peng , Choo Fook Hoong
DOI: 10.1109/ICIT.2015.7125280
关键词:
摘要: Hybridization of Energy Storages (ESs) with different characteristics is an effective and economic solution to enhance system performance. Hybrid Storage System (HESS) in centralized coordination normally implemented. To maintain operation case communication failure, a novel algorithm proposed for HESS distributed control this paper. DC bus voltage regarded as the global information carrier indication power balance. All ESs are configured slack terminals droop obtainment reference voltages. Localized Low Pass Filters (LPFs) added low ramp rates realize net decomposition scheduling manner. overcome disadvantages including deviation sharing errors, multi-level Management (EMS) applied. scheduled primary control. Bus restoration compensation implemented secondary Autonomous SoC recovery high applied tertiary Load shedding generation curtailment used limit range. MATLAB Simulink model developed verification method.