作者: Sang-Pil Ahn , Chul-Hwan Kim , Raj K Aggarwal , Allan T Johns
DOI: 10.1109/MPER.2001.4311325
关键词:
摘要: This paper presents a new concept, based on variable dead time control, in adaptive single pole auto-reclosing (SPAR). The proposed scheme can give rise to high rate of successful reclosing by adapting times. significance this algorithm is that it uses the waveform patterns voltage transients following initial breaker opening. performance method tested under variety fault locations Korean 765 kV system, and outcome study clearly indicates be used as an attractive effective means better management operation transmission system.