An Alternative Approach to Adaptive Single-Pole Auto Reclosing in High-Voltage Transmission Systems Based on Variable Dead Time Control

作者: Sang-Pil Ahn , Chul-Hwan Kim , Raj K Aggarwal , Allan T Johns

DOI: 10.1109/MPER.2001.4311325

关键词:

摘要: This paper presents a new concept, based on variable dead time control, in adaptive single pole auto-reclosing (SPAR). The proposed scheme can give rise to high rate of successful reclosing by adapting times. significance this algorithm is that it uses the waveform patterns voltage transients following initial breaker opening. performance method tested under variety fault locations Korean 765 kV system, and outcome study clearly indicates be used as an attractive effective means better management operation transmission system.

参考文章(9)
I Kim, A variable dead time circuit breaker auto-reclosing scheme using artificial neural networks International Journal of Electrical Power & Energy Systems. ,vol. 21, pp. 269- 277 ,(1999) , 10.1016/S0142-0615(98)00051-9
V.L. Buchholz, M. Nagpal, J.B. Neilson, R. Parsi-Feraidoonian, W. Zarecki, High impedance fault detection device tester IEEE Transactions on Power Delivery. ,vol. 11, pp. 184- 190 ,(1996) , 10.1109/61.484015
S.P. Websper, An investigation into breaker reclosure strategy for adaptive single pole autoreclosing IEE Proceedings - Generation, Transmission and Distribution. ,vol. 142, pp. 601- 607 ,(1995) , 10.1049/IP-GTD:19952250
A. Fakheri, T. Shuter, J. Schneider, C. Shih, Single Phase Switching Tests on the AEP 765 KV System-Extinction Time for Large Secondary Arc Currents IEEE Power & Energy Magazine. ,vol. 8, pp. 2775- 2783 ,(1983) , 10.1109/TPAS.1983.317960
I.K. Yu, Y.H. Song, Wavelet analysis and neural network based adaptive single-pole autoreclosure scheme for EHV transmission systems International Journal of Electrical Power & Energy Systems. ,vol. 20, pp. 465- 474 ,(1998) , 10.1016/S0142-0615(98)00015-5
A.T. Johns, Improved techniques for modelling fault arcs an faulted EHV transmission systems IEE Proceedings - Generation, Transmission and Distribution. ,vol. 141, pp. 148- 154 ,(1994) , 10.1049/IP-GTD:19949869
S. Goldberg, W.F. Horton, D. Tziouvaras, A computer model of the secondary arc in single phase operation of transmission lines IEEE Transactions on Power Delivery. ,vol. 4, pp. 286- 295 ,(1989) , 10.1109/61.19250
D.S. Fitton, R.W. Dunn, R.K. Aggarwal, A.T. Johns, A. Bennett, Design and implementation of an adapative single pole autoreclosure technique for transmission lines using artificial neural networks power engineering society summer meeting. ,vol. 11, pp. 748- 756 ,(1996) , 10.1109/61.489331