Stochastic harmonic analysis of mass rapid transit power systems with uncontrolled rectifiers

作者: C.S. Chen , H.J. Chuang , H.M. Shiau

DOI: 10.1049/IP-GTD:20030116

关键词:

摘要: The stochastic harmonic distortion of a mass rapid transit (MRT) system is investigated by considering the dynamic load behaviour train sets. A mathematical model 12-pulse uncontrolled rectifiers without interphase transformers derived and applied to flow analysis workout power demand injection currents at traction substations for each time snapshot. According mean values standard deviation currents, performed find average confidence interval voltage all buses. comparison with conventional analysis, which considers only current, reveals that method proposed can evaluate more accurately provide better guidance strategy mitigation.

参考文章(8)
Edward Wilson Kimbark, Direct current transmission. ,(1971)
Ying-Yi Hong, Lun-Hui Lee, Stochastic voltage-flicker power flow IEEE Transactions on Power Delivery. ,vol. 15, pp. 407- 411 ,(2000) , 10.1109/61.847281
M. Masood Hassan, E. Keith Stanek, Analysis Techniques in AC/DC Power Systems IEEE Transactions on Industry Applications. ,vol. IA-17, pp. 473- 480 ,(1981) , 10.1109/TIA.1981.4503985
Ke Li, State estimation for power distribution system and measurement impacts power engineering society summer meeting. ,vol. 11, pp. 911- 916 ,(1996) , 10.1109/59.496174
J.F. Dopazo, O.A. Klitin, A.M. Sasson, Stochastic load flows IEEE Transactions on Power Apparatus and Systems. ,vol. 94, pp. 299- 309 ,(1975) , 10.1109/T-PAS.1975.31855
H.C.J. Cornel, V.I. John, QENS-an enhanced version of the electric network simulator program IEEE Transactions on Vehicular Technology. ,vol. 40, pp. 273- 279 ,(1991) , 10.1109/25.69997
Y.-S. Tzeng, Harmonic analysis of parallel-connected 12-pulse uncontrolled rectifier without an interphase transformer IEE Proceedings - Electric Power Applications. ,vol. 145, pp. 253- 260 ,(1998) , 10.1049/IP-EPA:19981850