Structural capacity of a composite slim-floor beam with hollow steel tube shear connectors

作者: Mohamed S Majdub , Shahrizan Baharom , Ahmed W Al Zand , Azrul A Mutalib

DOI:

关键词:

摘要: A slim-floor composite beam’s structural performance relies on the composite action provided by shear connectors. However, the information on the performance of composite slim-floor beam with HSTs connectors in flexural in term of moment capacity, shear interaction and ductility still needs to be clarified. Thus, six specimens of the composite beams with square and rectangular HSTs with two different beam sections, I and inverted T, were tested. The main failure was found to be concrete crushing in the area of the connectors. HST connectors prevented the concrete slab from uplifting, particularly in the specimens without a top flange. Subsequently, this increased moment capacity to 230% and 152% for inverted T and I-beam sections, respectively. Furthermore, ductility behavior was also improved and met EC4 requirements. The degree of shear interaction was increased from 0.4 up to 0.9 compared to the beam …