Modeling of active beam units with Modelica

作者: Alessandro Maccarini , Göran Hultmark , Anders Vorre , Alireza Afshari , Niels C. Bergsøe

DOI: 10.1007/S12273-015-0236-5

关键词: Beam (structure)EngineeringMechanicsMean absolute percentage errorTerm (time)ThermalEmpirical equationsModelicaBuilding energy simulationBuilding energySimulation

摘要: This paper proposes an active beam model suitable for building energy simulations with the programming language Modelica. The encapsulates empirical equations derived by a novel terminal unit that operates low-temperature heating and high-temperature cooling systems. Measurements from full-scale experiment are used to compare thermal behavior of one predicted simulations. simulation results show corresponds closely actual operation. predicts outlet water temperature maximum mean absolute error 0.18 °C. In term percentage error, differ 0.9%. methodology presented is general enough be applied modeling other units.

参考文章(16)
Ala Hasan, Jarek Kurnitski, Kai Jokiranta, A combined low temperature water heating system consisting of radiators and floor heating Energy and Buildings. ,vol. 41, pp. 470- 479 ,(2009) , 10.1016/J.ENBUILD.2008.11.016
Arif Hepbasli, Low exergy (LowEx) heating and cooling systems for sustainable buildings and societies Renewable & Sustainable Energy Reviews. ,vol. 16, pp. 73- 104 ,(2012) , 10.1016/J.RSER.2011.07.138
Can Chen, Wenjian Cai, Karunagaran Giridharan, Youyi Wang, A hybrid dynamic modeling of active chilled beam terminal unit Applied Energy. ,vol. 128, pp. 133- 143 ,(2014) , 10.1016/J.APENERGY.2014.04.069
Johan Driesen, Juan Van Roy, Bart Verbruggen, Ideas for Tomorrow: New Tools for Integrated Building and District Modeling IEEE Power & Energy Magazine. ,vol. 11, pp. 75- 81 ,(2013) , 10.1109/MPE.2013.2268815
Can Chen, Wenjian Cai, Youyi Wang, Chen Lin, Performance comparison of heat exchangers with different circuitry arrangements for active chilled beam applications Energy and Buildings. ,vol. 79, pp. 164- 172 ,(2014) , 10.1016/J.ENBUILD.2014.04.048
Hannu Koskela, Henna Häggblom, Risto Kosonen, Mika Ruponen, None, Air distribution in office environment with asymmetric workstation layout using chilled beams Building and Environment. ,vol. 45, pp. 1923- 1931 ,(2010) , 10.1016/J.BUILDENV.2010.02.007
Michael Wetter, Wangda Zuo, Thierry S. Nouidui, Xiufeng Pang, Modelica Buildings Library Journal of Building Performance Simulation. ,vol. 7, pp. 253- 270 ,(2014) , 10.1080/19401493.2013.765506
Guangyu Cao, Markku Sivukari, Jarek Kurnitski, Mika Ruponen, Olli Seppänen, Particle Image Velocimetry (PIV) application in the measurement of indoor air distribution by an active chilled beam Building and Environment. ,vol. 45, pp. 1932- 1940 ,(2010) , 10.1016/J.BUILDENV.2009.11.020
Hideo Asada, EC Boelman, Exergy analysis of a low temperature radiant heating system Building Services Engineering Research and Technology. ,vol. 25, pp. 197- 209 ,(2004) , 10.1191/0143624404BT104OA