作者: Yinan Cui , Rajesh G. Kavasseri , Sukumar M. Brahma
DOI: 10.1109/TPWRD.2016.2615594
关键词: Particle filter 、 Step detection 、 Generator (circuit theory) 、 Stability (probability) 、 Phasor 、 Relay 、 Thévenin's theorem 、 Power (physics) 、 Control theory 、 Engineering
摘要: Out-of-step detection methods for generators depend on impedance measurements that are mapped from the angular difference between generator source and Thevenin equivalent of interconnected system. Though implemented successfully with decades operating experience, mapping is not most accurate due to a simplified model. This paper proposes an improved out-of-step method by means direct indicator—angular difference. The generator's rotor angle estimated particle filter-based dynamic state estimator separation then calculated combining raw local phasor this estimate. also enhanced real-time stability analysis able predict marginally unstable swings. approach illustrated via simulations New England 10-generator, 39-bus While consistent traditional schemes detection, proposed advantageous in it does make any simplifying assumptions its formulation, provides early swings resulting reduced stresses breaker generator. shows great potential supervise conventional relay availability synchrophasor computational power.