Full-Scale Water Mist Design Parameters Testing

作者: P. J. DiNenno , C. L. Beyler , G. G. Back , R. L. Hansen

DOI:

关键词:

摘要: Abstract : The overall objective of this evaluation was to further develop an understanding the capabilities and limitations water mist systems as applied machinery space applications. primary investigation evaluate applicability a local application test method being considered by International Maritime Organization (IMO). An effects spray obstructions on extinguishment performed. compartment parameters (size vent area), system (system flow rate), fire (heat release rate, type, location, degree obstruction) were evaluated aid in validating scalability model. This model can be used scale results other sized compartments. Local are capable extinguishing pan fires if they produce sufficient concentrations uniformly around protected object. They do have limited against obstructed fires. size obstruction separation distance between identified variables. A steady state validated that predicts temperatures, oxygen concentrations, critical sizes.