Evaluation Of Imo Fire Test Protocol For Fixed Gaseous - Fire Extinguishing Systems

作者: S. Nam , R. Hansen

DOI: 10.3801/IAFSS.FSS.6-469

关键词:

摘要: Six full-scale fire tests were conducted to evaluate a gaseous agent fixed extinguishing system for marine applications using the International Maritime Organization's MSC Circular 776fire test protocol, low temperature cylinder discharge test, and ver#i'catiorz side wall nozzles. The used was ~ 2 0 propelled by compressed nitrogen contained in same cylinders. verified that systems met performance requirenzents ternzs of time extinguishment times as specvied IMO protocol. cold which discharged from cylinders stored at -5 "C, also criteria. No adverse effect on performarzce observed. Agent time, effect, use are rliscussed. Recommendations made improve protocol regarding stabilization spray fires, additional telltale o f u reliable re-ignition source.

参考文章(2)
Eric W. Forssell, Gerard G. Back, Craig L. Beyler, Philip J. DiNenno, R. Hansen, D. Beene, An evaluation of the International Maritime Organization's gaseous agents test Protocol Fire Technology. ,vol. 37, pp. 37- 67 ,(2001) , 10.1023/A:1011697419034