作者: C.V. Nayar , S.J. Phillips , W.L. James , T.L. Pryor , D. Remmer
DOI: 10.1016/0038-092X(93)90043-N
关键词:
摘要: In most of the remote areas Australia and in many other parts world, diesel generators are used to provide electrical power. Such systems often characterised by either poor efficiency high maintenance costs because prolonged operation at low load levels, or intermittent power unit is only run during period significant load. The addition a battery bank conditioner produce diesel-battery-inverter hybrid system has been identified as produccing number benefits. can be broadly classified according their configuration series, switched, parallel systems. A new energy developed Western described this article. heart quality sinewave inverter which also operated reverse charger. cope with loads ranging from zero (inverter operation) approximately three times generator capacity operating parallel) excellent efficiency. fully automatic, provides continuous power, readily incorporate input wind photovoltaic This article includes description 5 kW charging part system, an economic analysis indicates favourable result for payback estimated order years.